The Discharge Site, the Display Site, and the Fallout Zone: What NFPA 1123 Actually Says

November 3, 2026

If you've spent any time doing permit work, you've probably run into situations where these three terms get used interchangeably. An AHJ asks for the "display site dimensions" and you sketch out your mortar rack footprint. A venue coordinator asks where the "fallout zone" is and you point at the same circle. It works out most of the time, but understanding what NFPA 1123 actually means by each of these terms matters when you're filling out a site plan, especially when someone's reviewing it who knows the code.

Let's break it down.

The Discharge Site

The discharge site is where the product is physically located for the show. Mortars, racks, shells staged for loading, your crew working the show. It's the operational footprint.

NFPA 1123 defines the discharge site as the location where the fireworks devices are actually fired from. This is a physical area that needs to be identified in your site plan, including the elevation of firing locations if product is being discharged from greater than 25 feet above ground level. If you're angling mortars for aesthetic reasons, the direction, tilt angle, and point of discharge all need to be documented.

This is also the area your crew occupies. It has to be kept clear of spectators, secured against unauthorized access, and large enough to work safely. For most ground-level outdoor displays, your discharge site is the crew perimeter around your mortar positions.

The Fallout Area

The fallout area is the designated zone where hazardous debris is expected to land after a device fires. Every shell has a fallout radius, which starts at the center point of the device and extends to the farthest point hazardous debris can reasonably reach. Draw a circle around that center point at that radius and you've got the fallout area.

Key word: hazardous debris. The code is specific about this. We're talking hot sparks, casing fragments, and unignited components. Confetti and lightweight novelty materials don't count. The fallout area is about where the dangerous stuff lands.

The fallout radius for aerial shells is directly tied to mortar size. A 3-inch shell requires a minimum secured site diameter of 420 feet for vertical mortars, meaning 210 feet of separation from the mortar center to the secured boundary in all directions. A 6-inch shell requires an 840-foot minimum secured diameter, or 420 feet of radius. Those numbers come straight from Table 5.1.3.1 in the 2022 edition. Angled mortars have different calculations, and chain-fused product follows a different set of minimums.

Something worth noting: the fallout area doesn't have to be centered on the discharge site. If you have room to work with, shifting mortar positions within the secured display site lets you relocate where fallout lands while maintaining required separation distances. That flexibility is built into the code, and it's exactly the kind of on-site adjustment that a good site plan needs to account for.

The Display Site

Here's where most people's mental model gets a little fuzzy.

By definition in NFPA 1123, the display site includes the discharge site, the fallout area, and the required separation distances. All three. The display site is the whole envelope.

So when the code says the display site shall have a radius at least as great as specified for the largest item in the display, it's talking about the entire secured area, not just where the mortars sit. For a vertical 6-inch shell, that's a minimum secured site diameter of 840 feet, meaning 420 feet from the mortar center to the secured boundary in every direction.

The display site and the fallout area can generally be considered the same thing, but there's an important distinction when your fallout area needs to be limited within a larger display site. In those cases, the specific location and dimensions of the fallout area need to be shown separately in the site plan so the AHJ can evaluate it properly.

The site plan itself has to document all of this: the dimensions of the display site, discharge locations, spectator viewing areas, parking areas, fallout areas, and the separation distances between them. If you're filing a permit and your site plan just shows a circle with mortars in the middle, you're probably leaving out information the AHJ needs to approve it.

Why It Matters for Your Site Plan

When an AHJ looks at a site plan, they're checking that the secured display site is large enough for the product being fired, that spectators are at or beyond the minimum separation distance, that the fallout area is positioned so hazardous debris won't land where people are, and that the whole thing is documentable and defensible.

Getting these three concepts right on paper protects you. A site plan that clearly identifies discharge positions, documents the fallout area with correct radii for each product size, and shows the full secured display site boundary is a site plan that's hard to reject and easy to defend if something ever goes sideways.

That's what Pyrositeplan is built to help you do. Auto-calculated safety radii based on mortar size, satellite imagery so your site plan reflects the actual location, and PDF exports formatted for permit submissions. The math is handled. The documentation is clean. You show up with a site plan that speaks the same language the code does.

Regulatory Disclaimer

This article is intended as a general reference only. All regulatory information should be independently verified against the current edition of the applicable NFPA standard. Nothing in this article should be interpreted as permission to deviate from code requirements. Requirements described as AHJ discretionary may vary by jurisdiction. Pyrositeplan makes no representation that this content reflects the most current edition of any referenced standard.